|
Electrical Cabling
Preferred AC Power System
To ensure that electrical noise produced by other
equipment does not create interference for the Aloha
System Hardware, all power conductors and
equipment-grounding conductors must be isolated from
other power circuits in the facility. To accomplish
this, the preferred method of providing power is the
installation of a power distribution panel intended for
the sole use of the Aloha System Hardware.
This dedicated power panel shall not be used to supply
other electrical loads in the facility. The panel will
be supplied by a feeder run directly from the main or
source panel for the facility.
Personal Computers, and/or Stand-alone devices are to be
powered from a single circuit, All branch circuits shall
include a separate neutral (ground conductor) and
equipment grounding conductor unless otherwise
indicated.
Notes on the Preferred AC Power System
Does not supplant national, state, or local electrical
codes. Each Branch Circuit shall be installed in a
dedicated ferrous metal conduit and have separate
neutral and ground conductors. Aluminum conduit is not
acceptable.
If the length exceeds 100 feet, increase all conductors
(including ground) one wire size for each additional 100
feet of length.
The neutral conductor from the main or source panel to
the dedicated Aloha panel is two sizes larger than the
phase conductors. The larger wire size is necessary to
accommodate the third harmonic current caused by the
switching power supplies in the Aloha User Workstations,
and to minimize the possibility of common mode noise
occurring on the power distribution circuits.
All power distribution circuits shall be installed in a
dedicated ferrous metal conduit that contains only the
Aloha supply and ground conductors. Data communication
cables shall be installed in separate ferrous metallic
conduits. All AC Power Receptacles shall be the
isolating ground type and shall be installed in
accordance with the specifications contained in the AC
Power Receptacles section.
Aloha approved Uninterruptible Power Supplies (UPS) are
required for each Aloha System Processor (provided with
the Aloha equipment package).
AC Power System Grounding
Proper grounding of the AC power system is critical to
achieve a high degree of equipment performance and
reliability- To minimize the introduction of electrical
noise, a separate equipment grounding system must be
installed. The specific grounding requirements are
outlined below.
ALOHA Power Panel Grounding
An insulated equipment grounding conductor (sized the
same as the supply conductors) shall be installed in the
same conduit as the supply conductors from the main or
source panel to the dedicated Aloha POS equipment panel.
This equipment grounding conductor is to be terminated
on the ground bus in the main panel. At the Aloha POS
equipment panel, install a ground bus that is
electrically isolated from the panel frame and terminate
the feeder equipment grounding conductor on this bus
bar. The metallic feeder conduit will be used as the
equipment grounding system for grounding the AC power
panel frame, metallic conduit system and metallic
junction boxes.
ALOHA Branch Circuit Grounding
Each branch circuit from the dedicated power panel to
the Aloha System Device receptacles shall include a full
size (same as supply conductors) insulated equipment
grounding conductor installed in the same conduit as the
supply conductors. The conduit must be dedicated to
Aloha equipment. This isolated grounding conductor shall
be terminated on the isolated ground bus bar in the
panel and on the equipment grounding terminal of a NEMA
IG5-15 isolated grounding type receptacle.
Alternate AC Power System
For existing construction where the existing facilities
do not justify the installation of a dedicated power
panel, an alternate method may be employed.
Notes on the Alternate AC Power System:
Does not supplant national, state, or local electrical
codes.
This method will provide power for all Aloha System
Hardware Devices directly from the MAIN or SOURCE power
panel. When using this method, it is imperative that no
system component be supplied from any power panel other
than the main or source panel.
All Aloha System hardware and system processor(s) shall
be supplied with circuits run directly from the main
panel.
Each branch circuit shall be installed in a dedicated
ferrous metal conduit and shall include a full sized
(same as the supply conductors) insulated equipment
grounding conductor installed in the same conduit.
Aluminum conduit is not an acceptable alternative to
ferrous metal. The isolated grounding conductors are to
be terminated directly at the ground bus in the main or
source panel. No grounding conductors shall be
terminated on any metallic conduit, water pipe, or
ground rod.
All AC Power Receptacles shall be the isolating ground
type and shall be installed in accordance with the
specifications contained in AC Power Receptacles
section. Aloha approved Uninterruptible Power Supplies
(UPS) are required for each Aloha System Processor
(provided with the Aloha equipment package).
Relaxed / Power Conditioned A C Power System
When providing the Preferred or Alternate AC Power
System is cost prohibitive and/or would require major
structural changes, we have defined a relaxed AC Power
System that may be used. However, the Preferred or
Alternate AC Power System is recommended by ALOHA.
The Relaxed/Power Conditioned AC Power System
is described as follows:
Aloha-approved Power Conditioners are required at all
Aloha Remote Printer locations (will be provided with
the Aloha equipment package).
Aloha-approved Uninterruptible Power Conditioners (UPC)
are required at each Aloha Personal Computer.
All Aloha AC Power branch circuits must originate from
the same "non-dedicated" Power Panel. This Panel must be
equipped with an "isolated" ground bus that is
electrically isolated from the panel frame and must be
provided with an insulated equipment grounding conductor
(sized the same as the supply conductors) which is
installed in the same conduit as the supply conductors
from the main or source power panel. The equipment
grounding conductor must be terminated on the ground bus
in the main or source panel and on the "isolated" ground
bus in the 'Non-Dedicated' Power Panel.
* Any Power Panel supplying heavy equipment within the
facility should not be selected as the "Non-Dedicated"
Power Panel supplying the Aloha equipment.
* Aloha AC Power Circuits must be "dedicated" for Aloha
equipment. No equipment other than Aloha Equipment may
be supplied by these "dedicated" circuits.
* Aloha AC Power Circuits must also be installed in a
dedicated conduit system. No circuits other than Aloha
circuits may exist in this dedicated conduit system. In
addition, the conduit used for the Aloha AC Power
Circuits must be ferrous metallic. Flexible, rigid, or
greenfield metallic conduit is acceptable. Aluminum
conduit is not acceptable.
Each "dedicated' Aloha AC Power circuit must include a M
size (same as supply conductors) insulated equipment
grounding conductor installed within the same
"dedicated" conduit system as the supply conductors.
This ground conductor must be terminated at the
"isolated" ground bus in the "non-dedicated" Power
Panel, and on the grounding terminal of each Isolated
Ground AC Power Receptacle.
All AC Power receptacles shall be the isolated ground
type and shall be installed in accordance with the
specifications contained in the AC Power Receptacles
section.
AC Power Receptacles
In order to maintain isolation of the equipment
grounding conductor from the conduit system, an isolated
ground receptacle must be used. This type of receptacle
(usually identified by an orange face) provides an
insulating barrier between the equipment grounding
terminal and the receptacle mounting strap. All branch
circuits from the Preferred, Alternate, and Relaxed/AC
Power Conditioned ALOHA power panel must be terminated
with isolated ground receptacles,
Standard receptacles bond the equipment grounding
terminal (green screw) to the receptacle mounting strap
and metallic conduit when the receptacle is mounted to
the box. This defeats the purpose of the isolated
grounding system. No equipment bonding jumper is to be
installed from the receptacle grounding terminal to the
outlet box.
NOTE: NEC Article 250-74, Exception 4 permits
installation of the isolated ground receptacles and
isolated equipment grounding conductors specified in
this section.
If a duplex receptacle is installed and only one socket
is to be used, the unused socket should be disconnected.
This is to prevent the temptation of using the outlet
for equipment that may produce extraneous ground
currents (e.g., floor buffers, vacuum cleaners, etc.).
The correct receptacle types are listed below.
Isolated Ground Receptacles RECEPTACLE TYPE NEMA P/N
125V., 15A., Simplex IG5-15RI 125V, 15A., Duplex
IG5-15R2
Abacus. You can count on us.
|