|
Planning
the System Cable Requirements
This section provides information on selecting and
installing the cables that connect Aloha hardware devices
to the PC Workstations and Ethernet LAN Hub.
View Wiring Diagram
Shielded
Cable vs. Metal Conduit
The
two main objectives when installing data transmission
cables are to prevent mechanical damage, and to prevent
disruptions due to outside electrical interference.
In general, a properly grounded ferrous metallic conduit
provides the best electrical and mechanical protection
but is more expensive to install, especially at an
existing site. Selection of a grounded ferrous metal
conduit vs. shielded cable requires consideration of
both expense and the degree to which occasional disruptions
can be tolerated.
All Aloha data transmission cables must be installed
within a separate grounded ferrous metal conduit when
the use of nonshielded cable is considered. Aluminum
conduit is not an acceptable alternative as it provides
little or no protection from Electromagnetic Interference
(EMI). The use of conduit must be continuous throughout
the system from junction box to junction box to ensure
a proper ground return path.
No
power cables or other communication cable shall be
run in the same conduit.
PVC
Conduit
PVC
Conduit can be employed when cables must be buried
below the floor level. Use metallic conduit for above
floor cable runs. When using PVC conduit, an Aloha
approved shielded data transmission cable must be used.
When installing PVC conduit in concrete flooring, the
following guidelines apply:
The PVC conduit should
be located at least six inches below the surface of
the floor.
The PVC conduit should
be located at least six inches from other nearby conduits.
If the PVC conduit
run is in the middle of a metal conduit run, a ground
wire must be run through the PVC conduit to connect
the metal conduit
together at both ends. This ensures a complete AC ground
path for the metal conduit.
No power cables or other communication cable shall
be run in the same conduit.
Mechanical
and Environmental Considerations
The
possibility of mechanical damage to cables is generally
apparent at the time of installation. This includes
outdoor runs of cable, as sunlight, rain and mechanical
flexing due to wind will cause the cable to deteriorate.
In these cases, it is strongly recommended that a grounded
ferrous metal conduit be used regardless of the threat
posed by the electrical phenomena listed below.
Lightning
Lightning
does not need to directly strike the cabling to cause
damage or disruption to the system. Nearby lightning
strikes produce strong electromagnetic fields, which
can induce voltages on the data transmission cables
causing disruptions or damage. A grounded ferrous metal
conduit should be employed for installations in geographical
areas subject to frequent thunderstorm activity. In
cases where shielded cables are used, the effects of
lightning can be reduced by placing the cable runs
as close to ground level as possible.
Electrical
Motors
Motors of various sizes are found in a typical restaurant
site. A grounded ferrous metal conduit should be employed
when cabling must be run at distances less than two
feet from motors that are 1/4 horsepower or smaller,
or less than six feet from motors larger than 1/4 horsepower.
Shielded cable can be considered if it is possible
to maintain the above minimum distances.
Radio
Frequency Interference (RFI)
The probability of Radio Frequency Interference varies
in accordance with many factors, including transmitter
power, its location, materials used in the construction
of the building, and physical placement of the power
and data transmission cables.
Other
possible causes of RFI include nearby amateur radio,
CB radios, radio-dispatched trucks and taxis, cordless
phones, and cordless headsets. As a general rule, a
grounded ferrous metal conduit should be employed when
the installation is within I mile of a broadcast transmitter
of any type,
As
with lightning, the effects of RFI can be minimized
by placing the cable runs as close to ground level
as possible.
Device
Location
The physical location of all devices in the Aloha POS
System must be determined. This information should
be provided as part of the restaurant blueprint showing
the locations of the hardware devices on the floor
plan, or riser diagram. From these sources of information,
you can determine both the number and types of cable
runs between the User Workstations (Server/Bar Terminals),
Manager's Workstation, Ethernet Hub (Located in the
Manager's Office close to the Manager's Workstation),
and Stand- alone Printer Devices (Broiler, Fry, Expediter,
Beverage Printers).
An
Aloha-approved Cat5- I OBaseT four-pair 24 gauge shielded
or non- shielded cable installed for all connections
between the Ethernet Hub, Manager's Workstation, and
Users Workstations (POS Terminals). If non- shielded
cable is used it must be installed in a grounded ferrous
metal conduit is required
The
same cable should be used for all connections between
the Stand Alone Printers and a Users Workstation (POS
Terminal). Each POS Terminal can drive one Local Printer
and one Stand-Alone Remote Printer.
When
more Stand-Alone Remote Printers are required than
the number of User Workstations (POS Terminals), additional
RS232 Communication Boards can be added to a User Workstation
(Provided with the Aloha Hardware Package)
Manager's
Workstation/Ethernet Hub
The hardware in the Manager's Office consists of a
PC Workstation (POS Server), PC Monitor, PC Keyboard,
Modem, Laser Reports Printer, and an Ethernet Hub,
and UPS.
Ethernet CAT5-IOBaseT cable- 4 pair-24 gauge twisted/shielded
or non- shielded cable from each Users Workstation
should be terminated in a patch panel next to the Server
computer. The Manager's Workstation will be attached
to the Ethernet Hub and cat 5 patch cables will be
used from the hub to the patch panel to connect the
terminals. If non-shielded cable is used it must be
installed in a grounded ferrous metal conduit is required.
User
Workstation (POS Terminals)
User
Workstation (POS Terminals) consist of a Personal Computer,
Touch Screen Monitor, Magnetic Credit Card Swipe Reader,
UPS and a RS232 Cable Connected Local Printer.
Ethernet
CAT5-IOBaseT cable- 4 pair-24 gauge twisted/shielded
or non-shielded cable is run from each Users Workstation
and terminated at the patch panel located in the Manager's
Office. Five feet of excess cable should be left outside
the data cable junction box to allow for a sufficient
length of cable for proper termination (POS Terminals
and Manager's Office). If non-shielded cable is used
it must be installed in a grounded ferrous metal conduit
is required
The
Communication Cable will be terminated at the User
Workstation with a Female RJ45 CAT5 plate/jack.
Stand-alone
(Remote) Printers
Stand-alone Printers consist of a Broiler, Fry, Expediter,
Beverage Printers and etc. The number of printers may
vary per restaurant.
Ethernet
CAT5-IOBaseT cable- 4 pair-24 gauge twisted/shielded or non-shielded
cable is used to connect stand-alone devices (e.g., Broiler,
Fry, Expediter, Beverage Printers, and etc.). The same pinouts
used for the terminals will also be used for the printer connections.
They are connected in a point-to-point configuration to a
Users Workstation (POS Terminal). Please note that
Stand Alone printer cable runs go from the POS Terminal to
the remote printer, these runs do not "home run"
to the office.
DCI
(Hardware provider) will provide the RJ-45 to DB-9
and RJ-45 to DB-25 connectors for the printers..
Five
feet of excess cable should be left outside the data
cable junction box to allow for a sufficient length
of cable for proper termination.
Aloha
Cables and Connectors
CABLE FOR ETERNET AND PRINTERS
Ethernet Cat5-10BaseT cable-4pair-24 guage twisted/shielded
Recommended Manufacturer:
Bertek (or an Equivalent Manufacturer)
For more
information on CAT5 cables please refer to our PDF
guide
ETHERNET
PLATE/JACK AND CONNECTORS
RJ45 Cat5 plate/jack for User Workstation Cable Termination
(one for each terminal, mounted in wall) Recommended
: Panduit's (or an Equivalent Manufacturer) Part Number:
MUJC588 or MFPD1EI
RJ45
Cat5 plate/jack for Ethernet Hub Cable Termination
(mounted in managers office wall)
Recommended:
Panduit's (or an Equivalent Manufacturer) Part Number:
MFPD4EL or MFPD1E1
ETHERNET CABLE WIRING CONNECTIONS PRINTER CABLE WIRING CONNECTIONS
Email
support questions to support@abacus-pos.com

|